Get yours in 5 daysHow it's calculated
One air change means a volume of air equal to the room is supplied (or exhausted) once. CFM is the airflow in cubic feet per minute; multiplying by 60 gives cubic feet per hour, and dividing by the room volume gives changes per hour. The right target depends on occupancy, heat load and contaminants.
- Room 40 × 25 × 10 = 10,000 ft³.
- Target 6 ACH.
- CFM = 6 × 10,000 ÷ 60 = 1,000 CFM.
Reference tables
Typical air-change targets by space
| Space | ACH |
|---|---|
| Office | 4–8 |
| Classroom | 6–12 |
| Restaurant kitchen | 15–30 |
| Warehouse | 4–6 |
| Restroom | 8–15 |
| Laboratory | 8–12 |
A number the tables do not give: a 10,000 ft³ office at 6 ACH needs 1,000 CFM — about a 20-inch round duct at 700 fpm.
See a live tool in action
The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:
FAQ
Is ACH the same as CFM?
No. CFM is raw airflow; ACH normalizes it to the room volume, so it tells you how quickly the whole room is refreshed.
What ACH should I target?
It depends on the space and code. Offices sit around 4–8, kitchens and labs are much higher. Use the table as a starting point and check the local mechanical code.
Does ceiling height matter?
Yes — volume is length × width × height, so a taller room needs proportionally more CFM for the same ACH.
Supply or exhaust?
Either can define ACH; balanced systems match them. For contaminant control, exhaust ACH is usually the governing number.