NEC 392.22 governs how much cable a tray may carry. The rule depends on cable size and tray type. Large power cables (≥1/0) go in a single layer so heat escapes, limited by the sum of their outside diameters. Smaller cables are limited by total cross-sectional area, which varies with tray inside width and whether other large cables share the tray.
- 12 in ladder tray; six 4/0 cables at 1.20 in Ø each.
- Σ diameters = 6 × 1.20 = 7.2 in.
- 7.2 in ≤ 12 in → compliant, single layer.
Reference tables
Allowable fill area — cables < 1/0 (NEC Table 392.22(A), ladder/ventilated ≤ 6 in usable depth)
| Tray inside width | Max fill area (in²) |
|---|---|
| 6 in | 7.0 |
| 12 in | 14.0 |
| 18 in | 21.0 |
| 24 in | 28.0 |
| 30 in | 35.0 |
| 36 in | 42.0 |
Method by cable size
| Cable size | Tray type | Fill rule |
|---|---|---|
| 1/0 and larger | Ladder / ventilated | Sum of diameters ≤ width, single layer |
| Smaller than 1/0 | Ladder / ventilated | Sum of areas ≤ Table 392.22(A) |
| Any | Solid bottom | Reduced allowances — see 392.22(A)(1)(d) |
A number the tables do not give: a 12 in ladder tray of 4/0 power cable at 1.20 in each fits about 10 cables in a single layer before you reach the width limit.
See a live tool in action
The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:
FAQ
Sum of diameters or fill area — which do I use?
Cable size decides it: 1/0 and larger power cables use sum-of-diameters in a single layer; anything smaller uses the allowable fill area from Table 392.22(A).
Does tray type change the answer?
Yes. Ladder and ventilated trays get the standard allowances; solid-bottom trays are reduced because they trap heat.
Do control and signal cables count?
They occupy area too. Mixed power and control installations have their own combined rules in 392.22(A); size the power cables first, then fit the rest into the remaining area.
Can I stack cables in layers?
Large power cables (≥1/0) must be a single layer. Smaller cables can fill by area up to the limit, which effectively allows some layering within the area budget.
Is fill the only tray limit?
No — you also derate cable ampacity for tray fill per 392.80. This tool checks the physical fill; ampacity is a separate step.