Duct Sizing Calculator

Turn an airflow into a duct size that stays quiet and efficient — by target velocity or by an equal-friction rate.

Short answerRound duct area (ft²) = CFM ÷ velocity (fpm); diameter (in) = √(576 × area ÷ π). Keep supply mains around 1,000–1,500 fpm, branches 600–900 fpm; the equal-friction method targets ~0.08–0.10 in.wg per 100 ft.

Want this on your own domain?

We build this calculator as an embeddable tool — engineered, SEO- and AI-ready, delivered in 5 business days for a flat $2,800.

Get yours in 5 days

How it's calculated

Airflow, velocity and cross-section are linked: area equals CFM divided by velocity. Pick a target velocity (lower is quieter, larger and costlier), compute the area, then the round diameter or an equivalent rectangular size. The equal-friction method instead holds a constant pressure loss per length.

Area(ft²) = CFM ÷ Velocity(fpm) Ø(in) = √( (Area × 144) × 4 ÷ π ) Equal friction ≈ 0.10 in.wg / 100 ft
Worked example
  1. 400 CFM branch at 800 fpm.
  2. Area = 400 ÷ 800 = 0.50 ft² (72 in²).
  3. Ø = 9.6 in → 10-inch round.

Reference tables

Round duct size at ~0.1 in.wg/100 ft (approx.)

CFMØ (in)
1006
2007
4009
60011
1,00013
1,50016
2,00018

Typical design velocities (fpm)

SectionVelocity
Main supply1,000–1,500
Branch600–900
Return700–1,000

A number the tables do not give: 400 CFM at 800 fpm equals a 10-inch round or roughly an 8×8-inch rectangular duct.

See a live tool in action

The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:

Conduit Fill · NEC▶ LIVE CALCULATOR Storage Rack quote-simulator▶ OPEN DEMO Packaging / box simulator▶ OPEN DEMO

FAQ

Velocity or equal-friction method?

Velocity is quick for a single run; equal-friction keeps a whole system balanced at a constant pressure loss. Most designs use equal-friction with velocity as a noise check.

Why keep velocity down?

High velocity means noise and more fan energy. The limits in the table keep ducts quiet without oversizing.

Round vs rectangular?

Round is the most efficient for a given area; rectangular fits tight spaces but needs a larger equivalent size for the same flow.

Does duct length change the size?

With equal-friction, longer runs accumulate more pressure loss, so long runs may need a size up to protect the fan.

This page is a reference aid. Always verify against ASHRAE / SMACNA methods and the applicable mechanical code. Figures shown are for orientation, not a stamped design.