Generator Sizing Calculator

Add running load and the biggest motor’s starting surge to size a generator that will not sag or stall.

Short answerRunning kW = sum of loads; kVA = kW ÷ power factor (0.8 typical). Then check the largest motor’s starting kVA (locked-rotor) so voltage does not dip — the starting requirement often sizes the set, not the running load.

Want this on your own domain?

We build this calculator as an embeddable tool — engineered, SEO- and AI-ready, delivered in 5 business days for a flat $2,800.

Get yours in 5 days

How it's calculated

Two demands size a generator. The steady running load in kW converts to kVA by the power factor. But motors draw several times their running current at start, so the largest motor’s inrush can dominate — the generator must supply that surge without excessive voltage dip. Take the larger of running and starting requirements.

kVA = kW ÷ PF Starting kVA ≈ motor HP × LRkVA factor size for max(running, starting)
Worked example
  1. 40 kW running ÷ 0.8 = 50 kVA.
  2. 20 HP motor start ≈ 120 kVA surge → governs.

Reference tables

Standard standby genset ratings (kW)

SmallMediumLarge
20100400
35150500
60200750

A number the tables do not give: a single 20 HP across-the-line motor start can demand ~120 kVA of surge — often more than the entire running load.

See a live tool in action

The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:

Conduit Fill · NEC▶ LIVE CALCULATOR Storage Rack quote-simulator▶ OPEN DEMO Packaging / box simulator▶ OPEN DEMO

FAQ

kW or kVA?

Loads are rated in kW (real power); generators and motor starting are limited by kVA. Convert with the power factor (kVA = kW ÷ PF).

Why does motor starting dominate?

Across-the-line motors draw 5–7× running current at start; that inrush can exceed the running load and set the generator size.

Can I reduce the starting size?

Yes — soft starters or VFDs cut inrush dramatically, letting a smaller generator serve the same motors.

Standby or prime rating?

Standby is for occasional outages; prime/continuous ratings are lower for full-time running. Match the rating to the duty.

This page is a reference aid. Always verify against the generator manufacturer data and NEC. Figures shown are for orientation, not a stamped design.