Two demands size a generator. The steady running load in kW converts to kVA by the power factor. But motors draw several times their running current at start, so the largest motor’s inrush can dominate — the generator must supply that surge without excessive voltage dip. Take the larger of running and starting requirements.
- 40 kW running ÷ 0.8 = 50 kVA.
- 20 HP motor start ≈ 120 kVA surge → governs.
Reference tables
Standard standby genset ratings (kW)
| Small | Medium | Large |
|---|---|---|
| 20 | 100 | 400 |
| 35 | 150 | 500 |
| 60 | 200 | 750 |
A number the tables do not give: a single 20 HP across-the-line motor start can demand ~120 kVA of surge — often more than the entire running load.
See a live tool in action
The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:
FAQ
kW or kVA?
Loads are rated in kW (real power); generators and motor starting are limited by kVA. Convert with the power factor (kVA = kW ÷ PF).
Why does motor starting dominate?
Across-the-line motors draw 5–7× running current at start; that inrush can exceed the running load and set the generator size.
Can I reduce the starting size?
Yes — soft starters or VFDs cut inrush dramatically, letting a smaller generator serve the same motors.
Standby or prime rating?
Standby is for occasional outages; prime/continuous ratings are lower for full-time running. Match the rating to the duty.