Pick the smallest conductor that carries your load after derating — sized to the right NEC temperature column and confirmed against the terminations.

Short answerChoose the smallest AWG/kcmil whose NEC 310.16 ampacity (at your insulation's temperature column) meets the load after ambient and conductor-bundle derating — then confirm the equipment termination rating (usually 75 °C).

Want this on your own domain?

We build this calculator as an embeddable tool — engineered, SEO- and AI-ready, delivered in 5 business days for a flat $2,800.

Get yours in 5 days

How it's calculated

Ampacity is the current a conductor can carry continuously without exceeding its insulation temperature rating. NEC Table 310.16 lists it by size, material, and insulation column (60/75/90 °C). Correction factors reduce it for high ambient temperature and for more than three current-carrying conductors bundled together; terminations then cap the usable column (commonly 75 °C).

Required ampacity = Load × 1.25 (continuous) · Derated ampacity = Table value × ambient factor × bundle factor Size = smallest conductor where Derated ampacity ≥ Required ampacity
Worked example
  1. Continuous load 40 A → 40 × 1.25 = 50 A design.
  2. THHN Cu, 75 °C terminations → 75 °C column.
  3. #8 Cu = 50 A at 75 °C ✓ (no derating needed).

Reference tables

Copper ampacity — NEC Table 310.16 (excerpt)

Size60 °C75 °C90 °C
#14151515
#12202025
#10303540
#8405055
#6556575
#4708595
1/0125150170
4/0195230260

Ambient temperature correction (90 °C column)

AmbientFactor
21–25 °C1.04
26–30 °C1.00
31–35 °C0.96
36–40 °C0.91
41–45 °C0.87

A number the code tables do not give directly: for 4–6 current-carrying conductors in one raceway, apply an 80% bundle factor before choosing the size.

See a live tool in action

The interactive version of this calculator is on our build queue. Meanwhile, these live example simulators show exactly how yours would look and behave on your own domain:

Conduit Fill · NEC▶ LIVE CALCULATOR Storage Rack quote-simulator▶ OPEN DEMO Packaging / box simulator▶ OPEN DEMO

FAQ

Which temperature column do I use?

Use the column that matches the lowest-rated part in the circuit — usually the equipment terminations. Most breakers and lugs are rated 75 °C, so even 90 °C wire is limited to the 75 °C ampacity for sizing.

Why multiply the load by 1.25?

NEC requires conductors and overcurrent devices for a continuous load (3 hours or more) to be sized at 125% of the load, so the equipment runs cool.

When does bundling derating apply?

When more than three current-carrying conductors share a raceway or cable, ampacity is reduced (e.g., 80% for 4–6, 70% for 7–9). Neutrals that carry current count.

Copper vs aluminum sizing?

Aluminum carries less per size, so you typically go up one or two sizes versus copper for the same load. Always confirm terminations are rated for aluminum.

Does this replace an engineered design?

No — it sizes conductors to Table 310.16 for orientation. Verify against the current NEC and your AHJ.

This page is a reference aid. Always verify against the current edition of the NEC (NFPA 70) and the authority having jurisdiction. Figures shown are for orientation, not a stamped design.